The formula
I = kVA × 1000 / (√3 × V) [three phase] | I = kVA × 1000 / V [single phase]
- kVA
- apparent power rating
- V
- line voltage
- √3
- 1.732 — present for three phase only
Worked example
A 100 kVA transformer on a 415 V three-phase system.
- I = 100 × 1000 / (1.732 × 415)
- I = 100000 / 718.8
- I = 139.12 A
139.12 A per line. Dropping the √3 would give 241 A — the classic three-phase mistake.
Where you'll use it
Sizing the cable and protection for a transformer or DG set, and checking whether an existing installation can take a new load. Note the current is set by kVA, not kW: a 100 kVA set at 0.8 power factor delivers 80 kW but still carries the full 139 A.