The formula
I_b ≤ I_n ≤ I_z
- I_b
- design current — what the circuit actually draws
- I_n
- breaker nominal rating, from the standard series 6, 10, 16, 20, 25, 32 A…
- I_z
- cable current capacity after derating
Worked example
A socket circuit drawing 18 A, wired in 4 mm² copper with a derated capacity of 26 A.
- Standard ratings at or above 18 A: 20, 25, 32 A…
- Of those, the ones at or below 26 A: 20 and 25 A
- Take the smallest: 20 A
- Check: 18 ≤ 20 ≤ 26 ✓
20 A, curve C, with a 30 mA RCCB — the sensitivity that protects a person rather than the wiring.
Where you'll use it
Every final circuit in a distribution board. Curve B trips at 3–5× rating for lighting and resistive loads; curve C at 5–10× for motors; curve D at 10–20× for transformers. When nothing fits, the fix is a bigger cable — never a bigger breaker.