The formula
I_sc = I_fl × 100 / %Z ; MVA_sc = MVA_rating × 100 / %Z ; κ = 1.02 + 0.98 e^(−3R/X)
- I_fl
- transformer full-load current = kVA × 1000 / (√3 × V)
- %Z
- nameplate percentage impedance — 4 to 6 % for LV distribution
- MVA_sc
- fault level; sources in series combine like parallel resistors
- κ
- IEC 60909 peak factor, 1.0 to 2.0, set by R/X at the fault
- i_p
- peak asymmetrical current = κ √2 I_sc — the make duty
Worked example
A 1000 kVA transformer, 415 V secondary, 5 % impedance, on a strong supply.
- I_fl = 1 000 000 / (√3 × 415) = 1391 A
- Multiplier = 100 / 5 = 20
- I_sc = 1391 × 20 = 27 824 A
- Fault level = 1.0 MVA × 20 = 20 MVA
27.8 kA symmetrical — which needs a 36 kA breaking capacity, the next standard size up.
Where you'll use it
Specifying breaking capacity for a switchboard, checking that an existing board is not under-rated after a transformer upgrade, and the symmetrical-fault question in every power systems paper. A cable run between the transformer and the board lowers the current usefully — but it lengthens the disconnection time too, so both ends have to be checked.