The formula
R₄₀ = R_measured × 2^((T − 40)/10) ; PI = R at 10 min / R at 1 min ; installation minimum = 1 MΩ per kV
- R₄₀
- resistance referred to the 40 °C reference, MΩ
- T
- winding temperature when the reading was taken, °C
- PI
- polarisation index — below 1 dangerous, 2 to 4 good
- V_test
- DC test voltage: 500 V below 1 kV, 5 kV at 11 kV (IEEE 43 Table 1)
Worked example
150 MΩ measured on a 415 V installation at 25 °C.
- Correction factor = 2^((25 − 40)/10) = 2^−1.5 = 0.354
- R₄₀ = 150 × 0.354 = 53.0 MΩ
- Minimum for a 415 V installation = 1 MΩ
- Test voltage for a winding under 1 kV = 500 V DC
53 MΩ corrected, comfortably above the 1 MΩ minimum — but the same 150 MΩ on an 11 kV machine at 20 °C corrects to 37.5 MΩ and fails a 100 MΩ limit.
Where you'll use it
Every megger test in a machines lab and every pre-commissioning check on a motor, cable or transformer. The trend across successive tests says far more than any single reading, and a failed test usually means moisture rather than damaged insulation — dry the winding and repeat before condemning it.