Contactor

Switchgear

An electromechanical switch rated for high current and frequent operation, used to switch motors, heaters, and lighting banks. Like a relay but built for industrial duty cycles and three-phase loads.

Schematic symbol

Relay

How contactor appears in a circuit diagram.

Types & variants

AC contactor (motor switching, 3-pole)DC contactor (battery / EV applications)Definite-purpose contactor (HVAC, lighting)Reversing contactor (two units, mechanically interlocked)Star-delta starter contactor setLatching / bistable contactor (pulse to switch, no hold current)Vacuum contactor (medium-voltage, contacts in vacuum bottle)

Key specs

Rated current (AC-3)

A

Current for motor switching. Common: 9A, 12A, 18A, 25A, 32A, 40A, 50A, 65A, 80A, 100A, 150A.

Coil voltage

V

Control voltage. Common: 24V DC, 24V AC, 230V AC, 400V AC.

Poles

3-pole for three-phase, 4-pole for switched neutral, 1- or 2-pole for DC.

Utilization category

AC-1 (resistive load), AC-3 (squirrel-cage motor, full voltage start), AC-4 (jogging/plugging).

Mechanical life

ops

10 million operations typical. Electrical life 1–3 million at full load.

Markings

Rated current (e.g. 32A), coil voltage (e.g. 230V 50Hz), AC-3 category, manufacturer (Schneider LC1, ABB AF, Siemens 3RT), auxiliary contact codes (NO/NC).

Standard values

Common frame sizes: 9A (small motors), 18A (1.5kW), 32A (5.5kW), 50A (11kW), 65A (15kW), 100A (22kW), 150A (45kW). Coil power: 2–10VA hold.

How to choose

1) Pick AC-3 current ≥ motor full-load current × 1.25. 2) Match coil voltage to your control circuit. 3) Select 3-pole for 3-phase motors. 4) Add auxiliary contacts if your control logic needs status feedback. 5) Add thermal overload relay for motor protection. 6) For frequent reversing, use a mechanically-interlocked reversing pair.

Pinout & package

DIN-rail or panel mount. Top: L1/L2/L3 in, T1/T2/T3 out (3-pole main contacts). Side/bottom: A1/A2 coil terminals. Snap-on front: auxiliary NO/NC contacts (e.g. 13-14 NO, 21-22 NC).

Example circuits

  • DOL (direct-on-line) motor starter with contactor + overload relay
  • Star-delta motor starter (3 contactors + timer)
  • Reversing starter for crane / hoist motor
  • Banks of high-bay lights switched by a PLC output via contactor
  • Heater bank control in industrial furnace

Common failures

Contact pitting / welding from arcing on switch-off (especially without arc suppressors). Coil burnout from overvoltage or holding at undervoltage. Mechanical jamming from dust or worn linkages. Buzzing/chattering from low coil voltage or dirty magnetic faces.

How to test

POWER ISOLATED. Check coil resistance (matches datasheet, usually 100–1000Ω). Manually press the armature — contacts should close with a solid click. Measure contact resistance closed (should be <0.1Ω). Inspect contacts for pitting. Apply rated coil voltage — should pull in cleanly.

Substitutes

Solid-state relay for DC or single-phase resistive loads (no moving parts but generates heat). Motor drive (VFD) if you need speed control as well as switching. Cannot substitute for high-current three-phase motor switching in most cases.