ElectroHub

Overload Relay

Protection

The motor's bodyguard: models motor heating and disconnects the contactor coil when sustained current says the windings are cooking. Trips on overload — deliberately slow, so it ignores normal starting inrush.

What it looks like

Overload Relay

A typical protection — exact shape, colour and markings vary between manufacturers.

Types & variants

Thermal (bimetal)ElectronicWith phase-loss sensitivityClass 10/20/30 trip curvesManual vs auto reset

Key specs

Current setting range

A

Adjustable dial — set to the motor's nameplate FLC.

Trip class

Class 10 trips in 10 s at 6× current; class 30 tolerates long starts.

Phase-loss protection

Detects a lost phase (single-phasing) — a top motor killer.

Auxiliary contacts

95-96 NC breaks the contactor coil; 97-98 NO for alarms.

Laws that govern it

  • Joule's law of heatingH = I² × R × t

    The bimetal is a thermal analogue of the motor winding: both heat as I²t, so the relay trips on the same curve the insulation would cook on.

  • Laws of resistanceR = ρ × L / A

    Bimetal strips work because two metals with different expansion (and their resistance heating) bend predictably with temperature.

  • Watt's lawP = V × I = I²R = V²/R

    Class 10 vs class 20 is how many seconds of that heating it tolerates — matched to whether the load starts quickly or slowly.

Each law is stated in full — with its diagram, variables and worked meaning — on the electrical laws page.

Markings

Amp dial, trip class, terminal numbers (95/96/97/98), test and reset buttons.

Standard values

Sold in overlapping ranges (e.g. 1.6–2.5 A, 2.5–4 A ...) that clip onto matching contactors.

How to choose

Range that puts nameplate FLC mid-dial, trip class matching start duration (high-inertia loads need class 20/30), phase-loss sensitive for three-phase, manual reset so trips get investigated.

Pinout & package

Clips under its contactor; power in from contactor T-terminals, motor out; control terminals 95-96 wired in series with the coil.

Example circuits

  • DOL starter: overload's 96 in series with contactor coil
  • 97-98 wired to a trip indicator lamp
  • Class 30 on a loaded conveyor start

Common failures

Nuisance trips from a setting below FLC or high ambient heat, welded mechanism after clearing a hard fault, and the human failure of cranking the dial to max to 'stop the tripping'.

How to test

Press TEST — the 95-96 contact should open (contactor drops). Verify the dial matches motor nameplate. True trip-time verification needs current injection.

Substitutes

Same range/class replacement matched to the contactor; electronic versions add accuracy and phase-loss detection in the same frame.

Where to buy