ElectroHub

PLC-controlled automatic star-delta starter with protection interlocks

Star-delta starting is the standard reduced-voltage start for a motor whose load is light at start-up, and implementing it in a PLC rather than with a mechanical timer turns it from a wiring exercise into a control project. This build runs the full sequence in ladder logic: main contactor and star contactor close together, the motor accelerates in star at a third of the direct-on-line current, the star contactor drops out, a deliberate dead time lets the arc clear, and the delta contactor closes. Around that sit the interlocks and the fault handling — because the one thing this circuit must never do is close the star and delta contactors together.

Electrical & Electronics (EEE)MechatronicsIndustrial automation & controlMachines & drivesProtection & switchgearHardware build
Rs 13,532 to Rs 53,295
All-in cost
3 weeks
With 3 of you
Diploma, B.E. mini
Usually taken as
10
Parts on the list

What it will really cost

Not just the parts. Teams budget from a component list, then run out in week six on wire, connectors and the driver board they destroyed. These are the lines that catch them.

Split betweenstudents
LineCost
Components and materials
From the bill of materials
Rs 10,340 to Rs 41,020
Spares and replacements
15 % — you will destroy something
Rs 1,551 to Rs 6,153
Consumables and hardware
Wire, connectors, headers, screws, heatshrink
Rs 1,241 to Rs 4,922
Report, printing and binding
Two or three bound copies, plots and the plagiarism check
Rs 400 to Rs 1,200
TotalRs 13,532 to Rs 53,295
Each, split 3 waysRs 4,511 to Rs 17,765

Indicative bands last checked in August 2026 — a guide, not a quotation. Prices move and vary by seller, and anything you can borrow from the lab comes straight off the total. The 3 week figure assumes 7 person-weeks of work shared between 3; students past 4 add coordination rather than output, so the estimate stops improving there.

Block diagram

tripStart, stop and emergency stop3-phase supply, MCB and isolatorPLC — ladder sequence and timersMain contactorStar contactorDelta contactorMotor with all six terminals outOverload relay in the winding path
  • Supply / source
  • Sensing
  • Control
  • Power stage
  • Load / output
  • Display & logging
  • Feedback path

The same chain in words

  1. 1Three-phase supply through an MCB and an isolator
  2. 2PLC with digital inputs and relay or transistor outputs
  3. 3Main, star and delta contactors with auxiliary contacts
  4. 4Electrical interlock: each contactor's normally closed auxiliary in the other's coil circuit
  5. 5Mechanical interlock between the star and delta contactors
  6. 6Overload relay with its trip contact wired to a PLC input
  7. 7Start and stop pushbuttons and an emergency stop
  8. 8Three-phase induction motor with all six winding terminals brought out

How it works

On the start command the PLC energises the main and star contactors together. The motor windings are connected in star, so each winding sees the line voltage divided by root three.

A timer runs for the star period while the motor accelerates. The period is set from how long the machine takes to approach its running speed on the actual load, not from a default value.

At the end of the star period the PLC de-energises the star contactor and starts a short dead-time timer. Nothing is energised into the delta path during this interval.

After the dead time the delta contactor is energised, the windings are reconnected in delta, and the motor runs at full voltage.

The overload relay trip contact, the emergency stop and both interlock auxiliaries are inputs to the logic, and any of them drops the whole sequence. The interlocks are also wired physically in the coil circuits, so the safe behaviour does not depend on the program being correct.

Design calculations

This is the chapter that separates an engineering project from an assembly job. Every value below carries the formula that produced it and the assumptions it rests on — check them against your own ratings before you use them, because your motor is not this motor.

Starting current ratio

About 3.7 A in star against 11 A direct on line

Star line current is one third of the delta line current

In star each winding sees V line divided by root three, so its current is down by that factor; and the line current in star equals the winding current, whereas in delta the line current is root three times the winding current. The two factors multiply to one third.

Starting torque ratio

One third of the direct-on-line torque

Torque is proportional to the square of winding voltage

This is why star-delta only suits loads that are light at start — pumps with a closed discharge valve, fans, unloaded compressors. A conveyor already carrying material will not accelerate in star, and the motor will sit drawing star-connected locked rotor current until the timer expires.

Motor full load current

7.3 A for a 3.7 kW (5 HP) motor at 415 V

I = P / (sqrt(3) x V x pf x efficiency)

3700 / (1.732 x 415 x 0.83 x 0.85) = 7.3 A. Use the nameplate value where one exists.

Contactor sizing

4.2 A through the main and delta contactors, 2.4 A through the star contactor

Main and delta contactors carry winding current, which is line current over root three

7.3 / 1.732 = 4.2 A, and the star contactor carries a third of the line current. In practice all three are bought as the same 9 A frame size, but knowing why they need not be identical is exactly what gets asked in the viva.

Dead time at transition

50 to 100 ms

Longer than the star contactor's release and arc-clearing time

Closing delta before star has fully opened puts the star point and the delta connection on the line at once, which is a direct short across the supply. This delay is the entire reason open transition starters exist.

Star period

Typically 5 to 10 s

Set from the machine's actual run-up time on its load

Too short and the transition happens at low speed, producing a current surge almost as large as a direct start. Too long and the motor sits at reduced torque, heating up without accelerating. Measure the run-up with a tachometer and set the timer from that.

Bill of materials

ItemQtyUnit cost
PLC
Micro PLC, at least 8 digital inputs and 6 outputs
Almost always the department's trainer kit — confirm availability before budgeting.
1Rs 4,500 to Rs 14,000
Contactors
9 A, 3 pole, 230 V AC coil, with auxiliary contact blocks
3Rs 500 to Rs 1,300
Mechanical interlock kit
Matched to the contactor series
1Rs 250 to Rs 700
Overload relay
Thermal overload, adjustable, set to the winding current
1Rs 600 to Rs 1,600
MCB and isolator
16 A four pole MCB, rotary isolator
1Rs 900 to Rs 2,200
Pushbuttons and E-stop
22 mm start, stop and latching emergency stop
1Rs 350 to Rs 900
Indicator lamps
22 mm LED indicators for star, delta, run and trip
4Rs 60 to Rs 180
Three-phase motor
3.7 kW (5 HP), 415 V, with all six terminals available
Machines lab motor. A motor with only three terminals brought out cannot be star-delta started at all.
1Rs 0 to Rs 12,000
Panel and DIN rail
Metal panel 400 x 500 mm, DIN rail, trunking
1Rs 1,500 to Rs 3,800
Wiring and terminals
2.5 sq mm wire, ferrules, terminal blocks, lugs
1Rs 500 to Rs 1,200

Specifications are written as ratings rather than brands, so any equivalent part works. Where a line says to borrow from the lab, do — it is usually the largest number on the page, and the total drops to Rs 9,032 at the low end without them.

What you need to be able to do

Skills

  • Mains & 3-phase wiring

None of these blocks you — they are learnable inside a semester. Each one you do not have costs a couple of weeks, so count them into your plan.

Equipment and access

  • PLC trainer kitrequired
  • Power electronics labrequired
  • Machines lab (motors, loading)

Anything marked required is a blocker, not a difficulty. Arrange the access before you commit to the project, not after.

What goes wrong

  • If the star and delta contactors ever close together the result is a phase-to-phase short across the supply. Wire the electrical interlock and fit the mechanical interlock before writing a single rung of ladder logic, and never rely on the program alone.
  • A motor with only three terminals in its terminal box cannot be star-delta started, because the winding ends are already internally connected. Check the motor before committing to this project.
  • PLC trainer kits are shared and often booked out for lab sessions. Confirm your access schedule early, because the panel wiring can be done in advance but the commissioning cannot.
  • The overload relay must be set for the winding current, not the line current, because in a star-delta starter it sits in the winding path. Setting it to the nameplate line current leaves the motor effectively unprotected.

How to make it a stronger project

Use these when your guide says the scope is too small, or when you want something in the results chapter that nobody else in your batch will have.

  • Add a closed transition using a transition resistor bank so the motor is never disconnected during changeover, and measure the reduction in the transition current surge.
  • Add an HMI screen showing the sequence state, run hours and trip history, which is what an industrial panel would carry.
  • Compare the measured starting current envelope against a direct-on-line start and a soft start on the same motor, and present all three on one graph.

Writing the report

The structure below is what a project report is marked against, with the mistake that costs marks in each chapter. There is no template to download and there will not be one: the writing is your work, and a site that did it for you would be helping you cheat rather than helping you pass.

A diploma report is typically 40 to 60 pages. The design and results chapters carry the marks; the literature survey can be short. A mini project report runs to about 40 to 50 pages, and the literature survey is usually brief. Guides expect one clear objective, met and measured.

The full report guide — front matter, conventions and page counts

Abstract

One paragraph covering what the problem is, what you built, and what the result was. Written last, even though it appears first.

Loses marks: Describing the problem and the method but never stating a result. If there is no number in your abstract, it is not finished.

Introduction

Why the problem matters, the context it sits in, and a clear statement of the objectives your project set out to meet.

Loses marks: Objectives written so vaguely that nobody can tell at the end whether they were met. Write objectives you can tick off in the conclusion.

Literature survey

What has already been done, what each approach achieved, and the specific gap your work addresses.

Loses marks: A list of paper summaries with no comparison and no gap. The survey exists to justify your design choice, so end it by saying what you chose and why.

Methodology and block diagram

The system as a whole: the block diagram, what each block does, and the signal or power path between them.

Loses marks: A block diagram copied from a datasheet or another report. Draw yours to match what you actually built, including the parts that are inconvenient.

Design and calculations

Every component value and rating, with the formula, the assumptions and the arithmetic that produced it. This is the chapter that distinguishes an engineering project from an assembly job.

Loses marks: Component values with no justification. If a resistor is 10 kOhm, the report must say why it is not 1 kOhm.

Hardware and software implementation

The circuit as built, the PCB or wiring, the flowchart, and the parts of the code that carry the actual logic.

Loses marks: Twenty pages of pasted source listing. Include the flowchart and the few functions that matter, and put the full listing in an appendix.

Results and discussion

What you measured, in tables and graphs, compared against what you predicted in the design chapter — including where they disagreed.

Loses marks: Photographs of the working model presented as results. A photograph is evidence that it exists, not evidence that it works. Results are measurements.

Conclusion and future scope

Whether each objective was met, what the measured performance was, and what the honest next step would be.

Loses marks: Future scope written as a wish list of unrelated features. It should follow from a limitation you actually hit.

References and appendices

Every source in a consistent style, plus datasheets, full code listings and the complete bill of materials.

Loses marks: Citing a blog or a video where a datasheet or a standard exists. Cite the primary source for anything you relied on.

Viva questions with answers

The demonstration is half the assessment. These are the questions this project invites, and the answers are written the way you would give them out loud.

Why does star connection reduce the starting current to one third?

Two effects multiply. In star each winding sees the line voltage divided by root three, so the winding current falls by that factor. And in star the line current equals the winding current, whereas in delta the line current is root three times the winding current. Together those give one third of the line current that a delta connection would draw.

Why does the starting torque also fall to one third?

Torque is proportional to the square of the winding voltage. In star that voltage is down by root three, and the square of one over root three is one third. So current and torque both fall to a third — the ratio of torque to current is unchanged, which is a fundamental limit of any reduced-voltage starting method.

What is the difference between open and closed transition?

Open transition disconnects the motor completely during the changeover, so the motor is momentarily unpowered and its residual flux can be out of phase with the supply when delta closes, producing a current surge. Closed transition keeps the motor connected through resistors during the changeover, so there is no disconnection and no surge, at the cost of extra contactors and a resistor bank.

Why is a dead time needed between star opening and delta closing?

Because a contactor takes tens of milliseconds to physically open and its arc takes longer still to extinguish. If delta closes while the star contacts are still conducting, the star point and the delta connections are both on the supply at once, which is a phase-to-phase short. The dead time guarantees that cannot happen.

Why must the overload relay be set to the winding current?

Because in a star-delta starter the overload relay is placed in the winding circuit, not the line, so the current flowing through it during normal running is the line current divided by root three. Setting it to the nameplate line current would mean it never trips until the motor is drawing about 1.7 times its rated current, which is not protection.

Why implement the interlock in hardware when the PLC program already prevents it?

Because a program can fail in ways wiring cannot — a corrupted output image, a scan that hangs with an output latched, or an output card whose transistor has failed short. The hardware interlock makes the dangerous state physically impossible regardless of the controller's state, and that is the principle behind every safety interlock in industrial practice.

Tools for the calculations above

Normally taken as a Diploma project (C-20, 6th sem) or B.E. mini project (5th/6th sem) project. If yours is a different course, the extensions above scope it up and the simpler half of the design scopes it down — the arithmetic does not change. Back to all projects.