MCB (Miniature Circuit Breaker)

Breaker

A resettable mains circuit breaker that trips on overload or short circuit, protecting house/building wiring. Replaces rewireable fuses; just switch it back on after a trip.

Schematic symbol

Switch (SPST)

How mcb (miniature circuit breaker) appears in a circuit diagram.

Types & variants

Type B (trips 3-5x, lighting/sockets)Type C (5-10x, motors/inductive)Type D (10-20x, high inrush)1P / 2P / 3P / 4P

Key specs

Rated current (In)

A

Continuous current, e.g. 6, 10, 16, 20, 32A.

Trip curve

B/C/D

Magnetic trip multiple for short-circuit response.

Breaking capacity (Icn)

kA

Max fault current it can interrupt, e.g. 6kA/10kA.

Poles

-

1P (live), 2P (live+neutral), 3P/4P for three-phase.

Markings

Front print like 'C16' = Type C, 16A; plus voltage (230/400V) and kA rating.

Standard values

6, 10, 16, 20, 25, 32, 40, 63A; Type B/C/D; 6kA or 10kA breaking.

How to choose

Size In to the cable's safe current (not the load) and coordinate with wire gauge. Type B for general/lighting, C for motors/AC, D for heavy inrush. Breaking capacity >= prospective fault current. Pair with an RCD/RCBO for shock protection.

Pinout & package

DIN-rail mount; line in (top), load out (bottom). MUST be installed by a qualified electrician - this is mains.

Example circuits

  • Final-circuit protection in a consumer unit/DB
  • Dedicated breaker for an AC or geyser (Type C)
  • RCBO = MCB + earth-leakage in one

Common failures

Nuisance tripping (under-rated or faulty), fails to trip (dangerous - replace), worn contacts, loose terminals causing heat.

How to test

Toggle on/off; use the test button on RCBOs. Proper trip testing needs a loop/RCD tester by an electrician. Discoloured terminals = overheating.

Substitutes

Same In, trip curve and >= breaking capacity, matching poles and brand DIN range. Do not up-size current to stop tripping.