Analog Panel Meters (PMMC / Moving Iron / Galvanometer)

Test Instrument

The needle instruments of the Measurements syllabus: the PMMC (D'Arsonval) movement behind every classic ammeter and voltmeter, its moving-iron sibling for AC, and the galvanometer they all descend from. Torque equations, shunts and multipliers — exam bread and butter.

What it looks like

Analog Panel Meters (PMMC / Moving Iron / Galvanometer)

A typical test instrument — exact shape, colour and markings vary between manufacturers.

Types & variants

PMMC / moving coil (DC only, linear scale)Moving iron (AC+DC, RMS-reading, cramped scale)Dynamometer type (AC/DC transfer instruments)Rectifier type (AC on a PMMC movement)Galvanometer (µA sensitivity, centre zero)Digital panel meters (LED replacements)

Key specs

Full-scale deflection

µA–A / mV–V

The movement's basic sensitivity — a typical PMMC movement is 50 µA/few-hundred mV FSD; everything bigger is shunts and multipliers.

Shunt / multiplier

Ω

Ammeter = movement + parallel shunt (Ish = I − Im); voltmeter = movement + series multiplier (Rs = V/Im − Rm). The two most-set numericals in the subject.

Accuracy class

class 0.5–2.5

Percent-of-FSD error class marked on the dial — class 1.0 panel meters are standard switchboard grade.

Ohms per volt

Ω/V

Voltmeter sensitivity = 1/Ifsd. A 20 kΩ/V meter loads circuits far less than a 1 kΩ/V one — the loading-effect exam question.

Damping & control

Spring control + eddy-current damping (PMMC) or air damping (MI): the deflecting/controlling/damping torque trio every viva asks.

Markings

Dial symbols tell all: a horseshoe magnet symbol = PMMC (DC), a curved iron piece = moving iron (AC/DC), class number, mounting position symbol, and the scale's own linearity reveals the type (square-law cramped start = MI).

Standard values

Switchboard meters: 96×96 mm or 72×72 mm squares, 0–500 V and CT-fed 0–5 A ranges (dial rescaled to the CT primary, e.g. 0–100 A via 100/5 CT). Education kits: 50 µA and 1 mA movements for building meters.

How to choose

1) DC circuits: PMMC — linear scale, high sensitivity, but reads average (wrong on AC unless rectifier type). 2) AC mains panels: moving iron — true RMS regardless of waveform, rugged, cheap. 3) Panel retrofits: digital LED meters with the same cutout size. 4) For lab meter-building: pick the movement, then compute shunt/multiplier. 5) CT/PT-fed meters must match the transformer secondary (5 A/110 V).

Pinout & package

Two terminals (+/− on DC types); switchboard cases mount through square panel cutouts with rear studs. Galvanometers add a mirror-and-lamp scale in lab versions. Shunts for large currents are external manganin blocks with millivolt leads.

Example circuits

  • Convert a 50 µA, 2 kΩ movement into a 0–10 V voltmeter (multiplier ≈ 198 kΩ) — the standard numerical
  • Ammeter + external 75 mV shunt reading 0–200 A on a battery charger
  • Ballistic galvanometer measuring charge in the magnetism lab
  • MI voltmeter + MI ammeter + dynamometer wattmeter around a single-phase load — the classic measurement bench

Common failures

Bent/sticking pointer from shock, open coil after gross overload (needle slams and dies), weakened magnet or fatigued springs reading low, and moisture-fogged dials. MI meters survive abuse that kills PMMC movements.

How to test

Zero-check mechanically (adjust screw), then compare against a trusted DMM at several points across the scale. A PMMC movement can be gently tested with a resistor-limited cell — full deflection at its rated µA. Check shunt/multiplier resistors when a rebuilt meter reads proportionally wrong.

Substitutes

Digital panel meters replace analog in the same cutouts (mind CT/shunt compatibility). PMMC-with-rectifier substitutes MI at low currents but mis-reads distorted waveforms. For trend-watching (tuning, nulling), many still prefer the needle — hence analog multimeters survive.